Gas-work authorisation and isolation procedure

BOUK-PRO-GAS · v1.0 · Completed fictional example · DOCX

Verify competent/registered specialists where required, isolate safely and obtain commissioning/handover evidence.

Download editable DOCXView this policy branch

Read-only preview. Use the downloaded native file for your own working copy. Examples are fictional; signatures, work releases and operational evidence remain separate.

BOUK-PRO-GAS | Version 1.0 | 23 October 2026 | GB baseline

COMPLETED FICTIONAL EXAMPLE. BuildOut UK Ltd is an illustrative construction business. The arrangements and cases below are examples for adaptation; no actual work, approval or signature is represented.

Verify competent/registered specialists where required, isolate safely and obtain commissioning/handover evidence.

Scope and operating responsibility

We apply this procedure to Refurbishment involving an existing gas installation. Evidence includes Service and installation information; contractor competence/registration as applicable; storage and heater assessment; isolation, test and commissioning hand-back. The role controlling the task checks applicability before mobilisation and whenever the scope changes.

RoleRequired action
Authorised specialist / appointed personOwn this arrangement, confirm competent support and maintain its evidence trail.
Project manager and Site managerCoordinate the actual package, provide resources and verify prerequisites before release; resolve occupied and subcontractor interfaces.
Trade supervisor and workersUse the accepted current method, demonstrate understanding, report changes and stop when critical safeguards are uncertain.
Competent specialist and H&S adviserProvide technical advice within competence; challenge evidence and identify limitations. Management retains the operating decision.

Inputs before using the procedure

Use the current project risk register, relevant survey and design revisions, equipment or product information, worker consultation and the task-specific records listed below. Resolve conflicting or missing information before relying on it. Do not fill missing technical values from an example.

How we carry out the arrangement

1 Plan and obtain reliable information

The competent appointed person identifies gas installations and services affected by alteration, excavation or temporary heating and coordinates with the asset owner and specialist contractor.

2 Verify capability and prerequisites

Only appropriately competent and, where legally required, registered people carry out gas work. A general construction qualification or permit does not authorise gas installation or commissioning.

3 Control work and interfaces

Temporary LPG or other combustion equipment is selected and located with suitable ventilation, flue/exhaust, fire, cylinder storage and occupied-space controls. Unvented or unsuitable appliances are not introduced as an informal heating fix.

4 Review change and safe handback

Isolation, leak concerns, tests, commissioning and hand-back are controlled by the appropriate specialist method. Staff are briefed on alarm, withdrawal and emergency reporting without attempting unauthorised repair.

Stop restrict and restart

Stop affected work at an unidentified service, suspected leak, uncertain isolation, unsuitable combustion appliance or unresolved ventilation/exhaust control; follow the gas emergency arrangement.

The person controlling the work makes the affected area safe and notifies the Site Manager. Restart requires the competent technical decision for the actual control, the authorised work-release decision and a fresh briefing of affected people. Record unresolved limits; an updated date or a completed form does not remove a hold.

Practical control detail

First ask whether the gas or hot-work task can be removed. Where it remains, reduce the potential release, contain and isolate the supply, control ignition and combustion, and plan for failure before relying on instructions or PPE.

Leave, avoid ignition and electrical switching, keep others away and prevent restart. GB natural gas emergency: 0800 111 999; NI natural gas emergency: 0800 002 001; LPG or cylinders: use the supplier emergency contact. Fire, immediate danger or medical emergency: 999. Read the full emergency and medical routes.

Evidence follow up and learning

Worked decision trail

Fictional situationDecision and evidence
What changesA specialist’s registration evidence does not cover the proposed appliance category.
ResponseThe Site Manager holds gas work while scope-specific competence and registration requirements are resolved.
VerificationCheck the actual engineer and work category, then retain competent testing and commissioning evidence without inventing results.

Supporting arrangement documents

ReferenceHow the document is used
BOUK-CHK-GAS-01
Gas specialist and work-scope authorisation check
Verify qualifications/registration scope, method and client interfaces.
BOUK-RA-GAS-01
LPG, temporary heating and gas-cylinder assessment
Control leaks, ventilation, ignition, storage and emergency response.
BOUK-FRM-GAS-01
Gas isolation, testing and handover evidence index
Index competent isolation, testing, commissioning and handover evidence.
BOUK-CHK-GAS-02
Gas appliance and cylinder condition check
Verify safe siting, protection, hose/regulator condition and controls.

Retain the record ID, task, location, competent author, revision, date, decision, restrictions, action owner and separate effectiveness evidence. Restrict personal and health information and apply the relevant retention rule. File genuine results separately from teaching examples.

Guidance Gas Safety at Work

Content basis

Built from the BuildOut policy and arrangement register, the SHARE policy/risk/routine-checklist/audit databases and the linked SHAREknowledge topics.

Register legal summaries retain their own review dates. No actual inspection, clinical record, specialist certificate or company approval is represented.